Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)

 
CURRENT MONITOR RELAYS
AC Plug-in
COP/COKP Series Overcurrent


  • Monitors AC single phase currents for overcurrent conditions
  • Adjustable time delay of 0.1-10 seconds on pick-up
  • Three separate current monitoring ranges covering 0.1 - 10 amperes
  • External CT can be used to extend ranges
  • Adjustable Pick-up Setting with either Fixed or Adjustable Drop-out Setting
  • LED indicates output relay status
  • Choice of compact 8 Pin SPDT or 11 Pin DPDT plug-in case
  • 10A output contacts

logo

800-238-7474
www.macromatic.com

COP10A62 COP10A62_side COKP10A62
Adjustable Pick-up, Fixed Drop-Out with Time Delay on Pick-up Adjustable Pick-up & Drop-Out with Time Delay on Pick-up

chartThe CO Series is used to detect an overcurrent condition. The pick-up current setting is user-adjustable within one of three ranges as shown in the Product Selection Table below. An external current transformer can be used to extend the range beyond 10 amperes.

Choose between a fixed drop-out current setting at 95% of the selected pick-up setting or an adjustable drop-out setting of 50-95% of the selected pick-up setting. The relay will energize when the monitored AC current is above the pick-up setting for a period longer than the adjustable time delay of 0.1-10 seconds. This delay prevents nuisance tripping caused by inrush currents. It will de-energize when the monitored AC current is below the drop-out setting.


8 Pin SPDT Plug-in
Pick-up
Setting
Drop-out
Setting
Input
Voltage
Current
Range Monitored
Product
Number
Wiring/
Socket
Adjustable
Across
Monitored
Range
Fixed
(at 95%
of Pick-up)
24VAC0.1 - 1A
0.5 - 5A
1 - 10A
COP01A68
COP05A68
COP10A68
8 Pin
70169-D
wiring diagram
Diagram 21
120VAC0.1 - 1A
0.5 - 5A
1 - 10A
COP01A62
COP05A62
COP10A62
Adjustable
Across
Monitored
Range
Adjustable
(From 50-95%
of Pick-up)
24VAC0.1 - 1A
0.5 - 5A
1 - 10A
COKP01A68
COKP05A68
COKP10A68
120VAC0.1 - 1A
0.5 - 5A
1 - 10A
COKP01A62
COKP05A62
COKP10A62

Click here for Sockets & Accessories.

11 Pin DPDT Plug-in
Pick-up
Setting
Drop-out
Setting
Input
Voltage
Current
Range Monitored
Product
Number
Wiring/
Socket
Adjustable
Across
Monitored
Range
Fixed
(at 95%
of Pick-up)
24VAC0.1 - 1A
0.5 - 5A
1 - 10A
COP01A28
COP05A28
COP10A28
11 Pin
70170-D
wiring diagram
Diagram 22
120VAC0.1 - 1A
0.5 - 5A
1 - 10A
COP01A22
COP05A22
COP10A22
Adjustable
Across
Monitored
Range
Adjustable
(From 50-95%
of Pick-up)
24VAC0.1 - 1A
0.5 - 5A
1 - 10A
COKP01A28
COKP05A28
COKP10A28
120VAC0.1 - 1A
0.5 - 5A
1 - 10A
COKP01A22
COKP05A22
COKP10A22

Click here for Sockets & Accessories.



APPLICATION INFORMATION DIMENSIONS
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.

Load (Burden): Less than 5VA

Current Settings:
Pick-up:Adjustable throughout current range monitored
Drop-out: Fixed at 95% of pick-up setting (COP Series); or Adjustable from 50-95% of pick-up setting (COKP Series)


Response Times: Pick-up: 100ms; Drop-out: 100ms

Indicator LED: Green when Input Voltage applied; Red when Relay is ON

Output Contacts: 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)

Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations

Temperature: -28o to 55o C (-18o to 131o F)

Insulation Voltage: 2,000 volts

Approvals:

c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg


dimension_img


Inches (Millimeters)

        Revised:  01/09

Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)