Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)

 
TIME DELAY RELAYS
Time Ranger TM Programmable Multi-Range
Plug-in


  • Each unit has 16 timing ranges built-in
  • Selecting a range is easy using a rotary switch (no math is required or DIP switches to set)
  • Timing ranges up to 2 hours (single time units) or 24 hours (dual time units)
  • Independently selectable & adjustable ON & OFF times on dual time products
  • Uses industry-standard 8 or 11 pin octal wiring diagrams
  • 10A DPDT output contacts

Timing Ranges

Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the unit and adjust within that range using the knob on top:

Single Time Units
Dial
Setting
Timing
Range
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
0.1 - 0.25 Sec.
0.2 - 0.5 Sec.
0.3 - 1 Sec.
0.5 - 2 Sec.
 1 - 4 Sec.
2 - 8 Sec.
 4 - 15 Sec.
8 - 30 Sec.
15 - 60 Sec.
30 - 120 Sec.
1 - 4 Min.
2 - 8 Min.
4 - 15 Min.
8 - 30 Min.
15 - 60 Min.
30 - 120 Min.

 

 

 

 

 

 

 

 

Timing Ranges

Select one of the 16 built-in time ranges by setting the rotary switch per a chart on the unit and adjust within that range using the knob on top:

Dual Time Units *
Dial
Setting
Timing
Range
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
0.6 - 2.5 Sec.
1.5 -5 Sec.
2.5 - 10 Sec.
5 - 21 Sec.
 10 - 42 Sec.
0.4 - 1.4 Min.
 0.7 - 2.8 Min.
1.5 - 5.5 Min.
3 - 11 Min.
5.5 - 22.5 Min.
11 - 45 Min.
0.4 - 1.5 Hr.
0.8 - 3 Hr.
1.5 - 6 Hr.
3 - 12 Hr.
6 - 24 Hr.

logo

800-238-7474
www.macromatic.com

TR-60222 TR-60222-side TR-63122
Single Time Dual Time

TR-6 Time Ranger Programmable plug-in time delay relays are flexible and reliable. The most common timing functions are available in all standard input voltages. Each product is offered with 16 timing ranges built in covering up to 2 hours (24 hours on dual time functions). Selecting a time range is easy using a rotary switch—no math is required or DIP switches to set. All dual-time functions such as repeat cycle or delayed interval have independently selectable and adjustable ON & OFF times for ultimate flexibility. These products utilize industry-standard 8 & 11 pin octal sockets, and have 10A DPDT output contacts.


Single Time Units (0.1 Sec - 2 Hr)
FUNCTIONINPUT
VOLTAGE
PRODUCT
NUMBER
WIRING/
SOCKETS
ON DELAY120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-60222
TR-60226
TR-60228
TR-60221
8 PIN OCTAL
70169-D

wiring diagram
DIAGRAM 1
INTERVAL ON120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-60522
TR-60526
TR-60528
TR-60521
FLASHER120VAC/DC
12V AC/DC
24V AC/DC
240V AC
TR-60822
TR-60826
TR-60828
TR-60821
OFF DELAY
Control Switch Trigger
120VAC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61622
TR-61626
TR-61628
TR-61621
11 PIN OCTAL
70170-D

wiring diagram
DIAGRAM 2
SINGLE SHOT
Control Switch Trigger
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61522
TR-61526
TR-61528
TR-61521
WATCHDOG
(Retriggerable
Single Shot)
Control Switch Trigger
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61322
TR-61326
TR-61328
TR-61321
OFF DELAY
Power Trigger
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61922
TR-61926
TR-61928
TR-61921
11 PIN OCTAL
70170-D
wiring diagram
DIAGRAM 4
SINGLE SHOT
Power Trigger
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61722
TR-61726
TR-61728
TR-61721
WATCHDOG
(Retriggerable
Single Shot)
Power Trigger
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-61822
TR-61826
TR-61828
TR-61821

Click here for Sockets & Accessories.

Standard Modifications such as External Time Adjust, Special Pin Configurations and Special Voltages are available-click here for more information or contact Macromatic for additional information.

Dual Time Units (0.6 Sec - 24 Hr) *
FUNCTIONINPUT
VOLTAGE
PRODUCT
NUMBER
WIRING/
SOCKETS
REPEAT CYCLE
(OFF Time First Followed by ON Time and Repeating)
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-63122
TR-63126
TR-63128
TR-63121
8 PIN OCTAL
70169-D
wiring diagram
DIAGRAM 1
REPEAT CYCLE
(ON Time First Followed by OFF Time and Repeating)
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-65122
TR-65126
TR-65128
TR-65121
DELAYED INTERVAL
(OFF Time Followed by ON Time Followed by OFF Until Reset)
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-66122
TR-66126
TR-66128
TR-66121
DELAYED INTERVAL
Control Switch Trigger
(OFF Time Followed by ON Time Followed by OFF Until Reset)
120V AC/DC
12V AC/DC
24V AC/DC
240V AC
TR-66522
TR-66526
TR-66528
TR-66521
11 PIN OCTAL
70170-D
wiring diagram
DIAGRAM 2

* All Dual Time Units have independently selectable & adjustable ON & OFF times.

Click here for Sockets & Accessories.

Standard Modifications such as External Time Adjust, Special Pin Configurations and Special Voltages are available-click here for more information or contact Macromatic for additional information.



APPLICATION INFORMATION DIMENSIONS
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.; DC Operation: +10/-15% of nominal.

Load (Burden): 2 VA

Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%; Minimum Setting (Adjustable): +0%, -50%. Fixed: > 2 Seconds: +1%, 0.1-2 Seconds: +5%

Repeat Accuracy (Constant Voltage & Temperature): > 2 Seconds Delay +0.1%; 0.1 - 2 Seconds Delay +2%

Reset Time: 0.1 Seconds

Output Contacts: 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),
1/3HP @ 120/240V AC (N.C.), B300 & R300

Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations

Temperature: (12-120V) -28o to 65o C (-18o to 150o F); 240V -28o to 50o C (-18o to 122o F)

Insulation Voltage: 2,000 volts

Approvals:

ur.gif  CSA_Logo.gif  CE_Logo.gif  UL-socket.jpg


dimension_img


Inches (Millimeters)

        Revised:  01/09

Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)