Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)

 
VOLTAGE MONITOR RELAYS
VAKPU Series Over/Undervoltage
Universal Voltage


  • Monitors any 208-240VAC single-phase voltage
  • Wide range of user-adjustable pick-up and drop-out settings
  • Adjustable time delay on both pick-up & drop-out of 0.1-10 seconds
  • LED indicates output relay status
  • Compact plug-in case utilizing industry standard 8 pin octal socket
  • 10A SPDT output contacts

logo

800-238-7474
www.macromatic.com

VAKPU VAKPU-side

chartOver/Under Voltage Relays provide protection to equipment where either an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.

The VAKPU Series can be used to monitor any 208-240V single phase voltage. The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. The drop-out setting is adjustable from 80-95% of the pick-up setting. The relay energizes when the monitored voltage is above the pick-up setting longer than the adjustable pick-up time delay (T1) of 0.1-10 seconds. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (T2), which is an adjustable 0.1- 10 seconds.


Adjustable Nominal Voltage Setting 208-240VAC
Adjustable Time Delay on Pick-up & Drop-out from 0.1 - 10 Seconds
NOMINAL
VOLTAGE
PICK-UP
VOLTAGE RANGE
DROP-OUT
VOLTAGE RANGE
PRODUCT
NUMBER
WIRING/
SOCKET
208-240VAC85-115% of Nominal Voltage Setting80-95% of Pick-up SettingVAKPU8 Pin Octal
70169-D
Wiring Diagram for Voltage Monitor Relay
DIAGRAM 150

Click here for Sockets & Accessories.



APPLICATION INFORMATION DIMENSIONS
Voltage Tolerance: +50%/-40% of nominal voltage; 50-60Hz; No supply (input) voltage is required.

Load (Burden): Less than 3VA

Voltage Settings:
Pick-up: Adjustable from 85-115% of nominal voltage
Drop-out: Adjustable from 80-95% of the Pick-up setting

Response Times:
Operate: Adjustable 0.1-10 Seconds
Release: Adjustable 0.1-10 Seconds

Indicator LED: Red Steady when Relay is energized; Green Steady when Relay is Off; and Gree Rapid Flashing when in power-up mode

Output Contacts: SPDT: 10A @ 240V AC/30V DC; 1/2HP @ 240V AC

Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations

Temperature: -28o to 65o C (-18o to 150o F)

Insulation Voltage: 2,000 volts

Approvals:

c-ur-us.jpg  UL-socket.jpg


dimension_img


Inches (Millimeters)

        Revised:  01/09