Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)

 
VOLTAGE MONITOR RELAYS
VAP/VAKP Series Over/Undervoltage
Adjustable Time Delay on Drop-out


  • Monitors AC single phase and DC voltages
  • Wide range of user-adjustable pick-up and drop-out settings
  • Adjustable time delay on drop-out of 0.5-10 seconds
  • LED indicates output relay status
  • Compact plug-in case utilizing industry standard 8 pin octal socket
  • 10A DPDT output contacts

logo

800-238-7474
www.macromatic.com

VAP120A VAP120A_side-1 VAKP120A
Adjustable Pick-up, Fixed Drop-Out Adjustable Pick-up & Drop-Out

chartOver/Under Voltage Relays provide protection to equipment where an over or under voltage condition is potentially damaging. They are designed to operate when the operating voltage reaches a preset value and drop-out when the operating voltage drops to a level below the preset value.

The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the VAP Series has a drop-out voltage setting fixed at 95% of the pick-up voltage setting. An adjustable drop-out setting of 75-95% of the pick-up setting is available on the VAKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (T), which is adjustable from 0.5-10 seconds for VA Series products. A time delay on drop-out fixed at 500ms is available (see VM Series).


Adjustable Pick-Up, Fixed Drop-Out Settings *
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
NOMINAL
VOLTAGE
PICK-UP
VOLTAGE RANGE
DROP-OUT
VOLTAGE RANGE
PRODUCT
NUMBER
WIRING/
SOCKET
24V AC
120V AC
21-27V AC
102-138V AC
20-26V AC
97-131V AC
VAP024A
VAP120A
8 Pin Octal
70169-D Wiring Diagram for Voltage Monitor Relay
DIAGRAM 20
12V DC
24V DC
48V DC
110V DC
10-14V DC
21-27V DC
41-55V DC
94-126V DC
9-13V DC
20-26V DC
39-52V DC
89-121V DC
VAP012D
VAP024D
VAP048D
VAP110D

* Drop-Out Voltage is fixed at 95% of the Pick-Up Setting.
Click here for Sockets & Accessories.

Adjustable Pick-Up & Drop-Out Settings *
Adjustable Time Delay on Drop-out from 0.5 - 10 Seconds
NOMINAL
VOLTAGE
PICK-UP
VOLTAGE RANGE
DROP-OUT
VOLTAGE RANGE
PRODUCT
NUMBER
WIRING/
SOCKET
24V AC
120V AC
21-27V AC
102-138V AC
16-26V AC
77-131V AC
VAKP024A
VAKP120A
8 Pin Octal
70169-D Wiring Diagram for Voltage Monitor Relay
DIAGRAM 20
12V DC
24V DC
48V DC
110V DC
10-14V DC
21-27V DC
41-55V DC
94-126V DC
8-13V DC
16-26V DC
32-52V DC
71-121V DC
VAKP012D
VAKP024D
VAKP048D
VAKP110D

* Drop-Out Voltage is adjustable from 75-95% of the Pick-Up Setting.
Click here for Sockets & Accessories.



APPLICATION INFORMATION DIMENSIONS
Voltage Tolerance: +25%/-50% of nominal voltage; AC voltages are 50-60Hz; No supply (input) voltage is required.

Load (Burden): Less than 3VA

Voltage Settings: Fixed at 95% of pick-up setting (VAP Series); Adjustable from 75-95% of pick-up setting (VAKP Series)

Response Times: Operate: 500 ms; Release: Fixed 500ms

Indicator LED: Red when Relay is ON; Green when Relay is Off

Output Contacts: 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)

Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations

Temperature: -28o to 55o C (-18o to 131o F)

Insulation Voltage: 2,000 volts

Approvals:

c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg


dimension_img


Inches (Millimeters)

        Revised:  01/09

Adobe Format of this Page  |   Home  |   Product Summary  |   Where to Buy   |   Instruction Sheet (Adobe)