The pick-up voltage setting is user-adjustable from 85-115% of the nominal voltage rating. As standard, the VMP Series has a drop-out voltage setting fixed at 95% of the pick-up voltage setting. An adjustable drop-out setting of 75-95% of the pick-up setting is available on the VMKP Series. The relay energizes when the monitored voltage is above the pick-up setting. The relay de-energizes when the monitored voltage is below the drop-out setting for a period longer than the drop-out time delay (T), which is a fixed 500ms for VM Series products. An adjustable time delay on drop-out of 0.5-10 seconds is available (see VA Series). |
||||||||||||||||||||||||||||
* Drop-Out Voltage is fixed at 95% of the Pick-Up Setting.
* Drop-Out Voltage is adjustable from 75-95% of the Pick-Up Setting. |
||||||||||||||||||||||||||||
| |||||||
|