Macromatic Industrial Control & Monitoring Products

PLP Series


Features
  • Protects against phase loss & phase reversal
  • Universal voltage range of 190-500V--greater range that covers more global applications
  • True RMS voltage measurement ensures accurate sensing across more applications
  • Retains fault indication and continues monitoring all voltages even with a lost phase
  • Full fault indication on top of unit for easy troubleshooting
Enclosure Style Plug-in case utilizing industry-standard 8 pin octal sockets
Configuration/
Contact Rating
  • SPDT
  • 10A @ 277V AC / 7A @ 30V DC;
    1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
Approvals       c-ur-us.jpg  CE_Logo.gif  UL-socket.jpg    UL File #E109466
Technical Documentation

Operation:

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. A phase loss or phase reversal condition will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.


plpu

Universal 190-500V Voltage Range

plpu-side

plpu-front

Full Fault Indication on Top for Easy Troubleshooting

Back to Product Line Summary         Home


3-PHASE MONITOR RELAYS