Product Specifications
ARP012A3R
picture
May not be exact product-for reference only
Catalog
Number
Function* Input
Voltage
Output Wiring / Sockets
ARP012A3R DPDT CROSS-WIRED 12 VAC 10A DPDT X WIRED diagram_img
Use Socket 70169-D

*DESCRIPTION OF FUNCTION CHART
In the off state, both the Lead Control Switch and the Lag Control Switch are open, the Alternating Relay is in the LOAD A position, and both loads are off. When the Lead Control Switch closes, it energizes the first load (M1). The red LED marked "LOAD A" glows. As long as the Lead Control Switch remains closed, M1 remains energized. If the Lag Control Switch closes, it energizes the second load (M2). When the Lag Control Switch opens, the second load (M2) is turned off. When the Lead Control Switch opens, the first load (M1) is turned off and the Alternating Relay toggles to the LOAD B position. When the Lead Control Switch closes, it turns on the second load (M2). The red LED marked "LOAD B" glows. If the Lag Control Switch closes, it will energize the first load (M1). When the Lag Control Switch opens, the first load (M1) is turned off. When the Lead Control Switch opens, the second load (M2) is turned off, the Alternating Relay toggles back to the LOAD A position, and the process can be repeated again. NOTE: if the Lag Control Switch does not close while the Lead Control Switch is closed, the Alternating Relay will act as a normal unit. func_chart

APPLICATION INFORMATION DIMENSIONS
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.

Load (Burden): Less than 3 VA

Indicator LEDs: Two LEDs marked LOAD A and LOAD B

Optional Selector Switch: ALTERNATE, LOAD A; LOAD B

Output Contacts: 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.)

Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations

Temperature: (Storage) -40o to 85o C (-40o to 185o F); (Operating) -28o to 65o C (-18o to 149o F)

Approvals:

ur.gif  CSA_Logo.gif  CE_Logo.gif  UL-socket.jpg


dimension_img


Inches (Millimeters)