Single-Probe Plug-in

LCP1A100F1

Lead Time: 7 Days

$106.57 (USD) / EACH

Description Of Function

Pump Up (Fill): When the liquid level falls below the probe, a fixed time delay begins & the LED flashes Red. This time delay prevents rapid cycling of the output relay & its load. At the end of the time delay, the output relay energizes & the LED is Red ON. The pump is ON to fill the tank. The relay remains energized until the liquid level rises & touches the probe. The output relay de-energizes, turning off the pump, and remains de-energized & the LED is Green ON until the liquid level falls below the probe.

Function Chart

function chart

Product Overview

Features
  • Controls Level of Conductive Liquids in Pump Up (Fill) or Pump Down (Drain) Applications
  • Probe is Pulsed with DC Voltage to Prevent Electrolysis
  • Two Adjustable Sensitivity Ranges
  • Input Voltages of 24, 120 & 240V
Enclosure Style

Plug-in case utilizing industry-standard 8 pin octal sockets

Configuration / Contact Rating
  • SPDT
  • 10A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
Application Information
  • Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.
  • Load (Burden): 2 VA
  • Indicator LEDs: Green ON with Input Voltage applied; Red Flashing during timing; Red ON when relay energized.
  • Probe Voltage: 5V DC Pulsed
  • Response Time: Pick-up: Fixed per value shown under "Function" in table above; Drop-out: 500ms
  • Output Contacts: 10A @ 240V AC/7A @ 28V DC, 1/4HP @ 120V AC (N.O.)
  • Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
  • Temperature: -28° to 65° C (-18° to 149° F)
Approvals

Operation

Pump Up (Fill): When the liquid level falls below the probe, a fixed time delay begins and the LED flashes Red.  This time delay prevents rapid cycling of the output relay and its load.  At the end of the time delay, the output relay energizes and the LED is Red ON. The pump is ON to fill the tank. The relay remains energized until the liquid level rises and touches the probe. The output relay de-energizes, turning off the pump, and remains de-energized and the LED is Green ON until the liquid level falls below the probe. 

Pump Down (Drain): When the liquid level rises and touches the probe, a fixed time delay begins and the LED fl ashes Red.  This time delay prevents rapid cycling of the output relay and its load.  At the end of the time delay, the output relay energizes and the LED is Red ON. The pump is ON to drain the tank. The relay remains energized until the liquid level falls below the probe level. The output relay de-energizes, turning off the pump, and remains de-energized and the LED is Green ON until the liquid level rises and touches the probe.

If the container is non-conductive or insulated, an additional probe must be installed as the COM connection where it will always be submerged.

You May Be Interested in These Other Products

  • Function: Multi-function (4): on delay, interval, off delay,single shot
  • Timing Range: Multi-range (4): 0.1 seconds - 100 minutes
  • Timing Range 2: None
  • Timing Adjustment: Analog
  • Control Voltage: Universal: 24-240V AC and 12-125V DC
  • Output: 10A SPDT
  • Enclosure Type: Encapsulated
  • Standard Modifications: None
  • Remote Potentiometer: None
  • Remote Potentiometer 2: None
$95.97
  • Function: Operating configuration independently applied to each channel
  • Control Voltage: Universal: 102-132V AC & 10-125V DC
  • Number Of Channels: 4-channel
  • Enclosure Style: 60mm DIN-Rail
  • Standard Modifications: None
$611.26
  • Control Voltage: 24V AC/DC (GS024C Relay & SS024 Socket)
  • Output: 6A 1 Form C
  • Options: None
  • Terminal Configuration: Slim (Pre-mounted with Socket)
$15.02
  • Communication Platform: Modbus TCP
  • Monitored Voltage: 190-600V AC
  • Output: 5A SPDT
  • Protection: Phase Loss, Phase Reversal, Voltage Unbalance, Undervoltage & Overvoltage
  • Standard Modifications: Local Adjustment (PC1MDUL);
  • Enclosure Style: DIN-Rail
$550.08