PAP Series

PAP208

Lead Time: 7 Days

$104.23 (USD) / EACH

Description Of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. Any one of three fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting (see right).

Function Chart

function chart

Product Overview

Features
  • Protects against phase loss, phase reversal & undervoltage
  • Separate 208, 240, 400, 480V & 575V versions
  • True RMS voltage measurement ensures accurate sensing across more applications
  • Retains fault indication and continues monitoring all voltages even with a lost phase
  • Best-in-class phase loss protection
  • Full fault indication on top of unit for easy troubleshooting
Enclosure Style

Plug-in case utilizing industry-standard 8 or 11 pin octal sockets

Configuration / Contact Rating
  • SPDT/DPDT
  • 10A @ 277V AC / 7A @ 30V DC / 5A @ 277V AC / 5A @ 30V DC
Application Information
  • Load (Burden): Less than 40 VA
  • Response Times:
    Power Up/Restart After Fault: Fixed at 1 Seconds
    Drop-out Due to:
      Phase Loss & Reversal:
      Undervoltage:

    100ms Fixed
    Fixed 4 Seconds
  • Minimum/Maximum Voltage: 156-198V (PAP208); 180-230V (PAP240); 330-380V (PAP400); 360-460V (PAP480); 431-546V (PAP575), all 50/60Hz. ±5%
  • Reset: Automatic upon correction of fault.
  • Output Contacts: 10A @ 277V AC / 7A @ 30V DC; DPDT 5A @ 277V AC, 5A@30V DC, 1/3HP @ 120/240V AC, B300 Pilot Duty
    1HP @ 250V AC, 1/2HP @ 125V AC, C300 Pilot Duty
  • Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Temperature: -28° to 65° C (-18° to 149° F)
Approvals

Operation

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized. Any one of three fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

You May Be Interested in These Other Products

  • Function: Delayed interval (switch trigger)
  • Timing Range: Multi-range (16): 0.05 seconds to 100 hours
  • Timing Range 2: Multi-range (16): 0.05 seconds - 100 hours
  • Timing Adjustment: Analog
  • Control Voltage: Universal: 24-240V AC and 12-125V DC
  • Output: 10A DPDT
  • Enclosure Type: Plug-in
  • Standard Modifications: None
  • Remote Potentiometer: None
  • Remote Potentiometer 2: None
$127.29
  • Function: Overcurrent AC only
  • Control Voltage: 120V AC
  • Output: 10A SPDT
  • Trip Delay: None
  • Enclosure Style: Plug-in
  • Current Range: 0.5 - 5A
  • Sensing Delay On Power: 0.1 - 10 seconds
$141.22
  • Control Voltage: 120V AC
  • Output: 4 Form C Contacts
  • Options: Standard (LED and Push-to-Test Included)
  • Terminal Configuration: Blade
$14.51