PC Series

PC1MDUL

Lead Time: In Stock

$550.08 (USD) / EACH

Description Of Function

As standard the PC Series Relays are in the Automatic Reset mode. However, they can be set to Manual Reset mode by connecting a momentary N.C. switch across terminals 5 and 6. Upon application of control voltage, the PC Series will go into Manual Reset mode if it recognizes an N.C. switch across terminals 5 and 6. The N.C. switch must be opened (pressed) to reset the relay and resume normal operation after either a fault clears or after each power-up when the unit is in Manual Reset mode.

Function Chart

function chart

Product Overview

Features
  • Three-Phase Monitor Relays provide real-time status and measurement via Modbus TCP
  • Communication makes data available for continuous monitoring, real time alerts and intelligent troubleshooting of voltage systems
  • Real time data improves decision making within smart control systems
  • Protects against phase loss, phase reversal, phase unbalance, undervoltage and overvoltage 
  • True RMS voltage measurement ensures more accurate measurement regardless of load type or wave shape
  • LED status indication on front face for easy troubleshooting
  • Universal monitored voltage:190 - 600V AC (50/60Hz)
  • Control voltage: 102 - 132V AC; 10 - 132V DC
Enclosure Style

Mounts on 35mm DIN-rail or screw mounting with extendable clips

Configuration / Contact Rating
  • SPDT 5 A @ 250V AC, General Purpose;
  • 5 A @ 24V DC, Resistive;
  • 1/4HP @ 120V AC (N.O.)
    Minimum recommended:
  • 12V DC @ 100 mA
Application Information
  • Load (Burden): 3VA
  • Monitored Range: 190 - 600V AC
  • Control Voltage: 102 - 132V AC; 10 - 132V DC
  • Life: Electrical - 100,000 closures @ full load; 360 operations per hour max. frequency; Mechanical - 30 million closures @ no load; 72,000 operations per hour max. frequency
  • Temperature: Operating, -28° to 65° C (-18° to 149° F) Storage, -25° to 75° C (-40° to 185° F)
Approvals
UL #: E109466

Operation

Phase Loss: Unit trips on loss of any Phase L1, L2 or L3, regardless of any regenerative voltages.

Phase Reversal (Out-of-Sequence): Unit trips if sequence (rotation) of the three phases is anything other than L1-L2-L3. It will not work on L3-L2-L1.

Phase Unbalance: Adjustable from 2 - 10% unbalance. Unit trips when any one of the three lines deviates from the average of all three lines by more than the adjusted set point for a period longer than the adjustable trip delay. It will reset at 80% of the unbalance trip setting.

 

PC1MDUL-Status-LED-Chrt

 

Undervoltage: Adjustable from 80-95% of the line voltage setting. Unit trips when the average of all three lines is less than the adjusted set point for a period longer than the adjustable trip delay. It will reset at +2% of the undervoltage trip setting.

Overvoltage: Adjustable from 105-120% of the line voltage setting. Unit trips when the average of all three lines is greater than the adjusted set point for a period longer than the adjustable trip delay. It will reset at -2% of the overvoltage trip setting.

Modbus TCP:

Connector: RJ45

Connection speed: 10/100 Mb Full and Half Duplex

IP Addressing: Static (default), Dynamic (DHCP)

IP Configuration (KBA) >

You May Be Interested in These Other Products

  • Function: Multi-function (10): on delay, flasher cycle off 1st, flasher cycle on 1st, interval, off delay, retriggerable one shot (watchdog), pulse generator (plus=0.5 seconds, one shot, on/off delay, memory latch
  • Timing Range: Multi-range (8): 0.1 seconds - 10 days
  • Timing Range 2: None
  • Timing Adjustment: Analog
  • Control Voltage: Universal: 12 - 240V AC/DC
  • Output: 15A SPDT
  • Enclosure Type: 17.5mm DIN-Rail
  • Standard Modifications: None
  • Remote Potentiometer: None
  • Remote Potentiometer 2: None
$101.84
  • Function: Overcurrent AC only
  • Control Voltage: 120V AC
  • Output: 10A SPDT
  • Trip Delay: None
  • Enclosure Style: Plug-in
  • Current Range: 0.5 - 5A
  • Sensing Delay On Power: 0.1 - 10 seconds
$141.22
  • Control Voltage: 120V AC/DC ( GS060C Relay & SS120 Socket)
  • Output: 6A 1 Form C
  • Options: None
  • Terminal Configuration: Slim (Pre-mounted with Socket)