PMP120-X
Lead Time: 7 Days
Description Of Function
When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting. See Function Chart.
Function Chart

Product Overview
Features
- The PMP-X Series provides an additional SPNO contact to signal PLC, SCAD, or other system.
- Protects against phase loss, phase reversal, phase unbalance, undervoltage, overvoltage & rapid cycling
- True RMS voltage measurement ensures accurate sensing across more applications
- Retains fault indication and continues monitoring all voltages even with a lost phase
- Ultimate three-phase protection with a variety of user-selectable and adjustable settings
- Full fault indication on top of unit for easy troubleshooting
Enclosure Style
Plug-in case utilizing industry-standard 8 pin octal sockets
Configuration / Contact Rating
5A SPDT + 5A SPNO
Application Information
- Load (Burden): Less than 40 VA
- Response Times:
Power Up/Restart After Fault: 1-300 Seconds Adjustable Drop-out Due to:
Phase Loss & Reversal
Phase Unbalance
Undervoltage
Overvoltage
100ms Fixed
0.3 - 30 Seconds Adjustable
0.3 - 30 Seconds Adjustable
0.3 - 30 Seconds Adjustable - Minimum/Maximum Voltage: 156-550V (PMPU-X); 77-152V (PMP120-X): 345-660V (PMP575-X), 50-60Hz. ±5%
- Reset: Automatic after a fault clears, and the restart delay is completed.
- Output Contacts: 5A @ 277V AC / 5A @ 30V DC; 1/3HP @ 120/240V AC, B300 Pilot Duty
- Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
- Temperature: -28° to 65° C (-18° to 149° F)
Operation
When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.