PMP-X Series

PMP120-X

Lead Time: 7 Days

$222.68 (USD) / EACH

Description Of Function

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting. See Function Chart.

Function Chart

Product Overview

Features
  • The PMP-X Series provides an additional SPNO contact to signal PLC, SCAD, or other system.
  • Protects against phase loss, phase reversal, phase unbalance, undervoltage, overvoltage & rapid cycling
  • True RMS voltage measurement ensures accurate sensing across more applications
  • Retains fault indication and continues monitoring all voltages even with a lost phase
  • Ultimate three-phase protection with a variety of user-selectable and adjustable settings
  • Full fault indication on top of unit for easy troubleshooting
Enclosure Style

Plug-in case utilizing industry-standard 8 pin octal sockets

Configuration / Contact Rating

5A SPDT + 5A SPNO

Application Information
  • Load (Burden): Less than 40 VA
  • Response Times:
    Power Up/Restart After Fault: 1-300 Seconds Adjustable
    Drop-out Due to:
      Phase Loss & Reversal
      Phase Unbalance
      Undervoltage
      Overvoltage

    100ms Fixed
    0.3 - 30 Seconds Adjustable
    0.3 - 30 Seconds Adjustable
    0.3 - 30 Seconds Adjustable
  • Minimum/Maximum Voltage: 156-550V (PMPU-X); 77-152V (PMP120-X): 345-660V (PMP575-X), 50-60Hz. ±5%
  • Reset: Automatic after a fault clears, and the restart delay is completed.
  • Output Contacts: 5A @ 277V AC / 5A @ 30V DC; 1/3HP @ 120/240V AC, B300 Pilot Duty
  • Life: Mechanical: 10,000,000 operations, Full Load: 100,000 operations
  • Temperature: -28° to 65° C (-18° to 149° F)
Approvals
UL #: E109466

Operation

When the proper 3-phase line voltage is applied to the unit and the phase sequence (rotation) is correct, the relay is energized after the Restart Delay is completed. Any one of five fault conditions will de-energize the relay after a delay. Re-energization is automatic upon correction of the fault condition. A bi-color status LED indicates normal condition and also provides specific fault indication to simplify troubleshooting.

You May Be Interested in These Other Products

  • Function: Delayed interval (switch trigger)
  • Timing Range: Multi-range (16): 0.05 seconds to 100 hours
  • Timing Range 2: Multi-range (16): 0.05 seconds - 100 hours
  • Timing Adjustment: Analog
  • Control Voltage: Universal: 24-240V AC and 12-125V DC
  • Output: 10A DPDT
  • Enclosure Type: Plug-in
  • Standard Modifications: None
  • Remote Potentiometer: None
  • Remote Potentiometer 2: None
$127.29
  • Function: Overcurrent AC only
  • Control Voltage: 120V AC
  • Output: 10A SPDT
  • Trip Delay: None
  • Enclosure Style: Plug-in
  • Current Range: 0.5 - 5A
  • Sensing Delay On Power: 0.1 - 10 seconds
$141.22
  • Control Voltage: 120V AC
  • Output: 4 Form C Contacts
  • Options: Standard (LED and Push-to-Test Included)
  • Terminal Configuration: Blade
$14.51