TE-8816U
Lead Time: In Stock
Description Of Function
TE-881 products have 10 functions built-in. The operation of each one is shown at right.
Function Chart

Product Overview
Application Information
- Voltage Tolerance: -15% of 12V, +10% of 240V
- Load (Burden): 3VA (AC), 1.7W (DC)
- Repeat Accuracy (Constant Voltage & Temperature): +0.2%
- Reset Time: 0.150 Seconds
- Indicator LED: Green-Input Voltage; Red (Flashing)-Timing or Red (Steady)-Relay ON
- Output Contacts: 15A @ 240V AC, 1/3HP @ 120V AC, 3/4HP @ 240V AC, B300
- Life: Mechanical: 10,000,000 operations; Full Load: 70,000 operations
- Temperature: -20° to 55° C (-4° to 131° F)
File Downloads
-
Digital Catalog
-
TE eCAD Package
CAD Drawing
-
901-0000-281 TE-88 Series Installation Instructions
Instruction Sheet