THS-1 Series (F31 Dual R1-Onboard)

THS-1314A-02R1-04

Lead Time: 10 Days

$92.33 (USD) / EACH

Description Of Function

Upon application of input voltage, the time delay (t1) begins. At the end of the time delay (t1), the output is energized and remains in that condition for the time delay (t2). At the end of this time delay, the output is de-energized and the sequence repeats until input voltage is removed.

Function Chart

Product Overview

Features
  • Cost effective design & compact 2" x 2" enclosure are ideal for industrial applications
  • Microprocessor-based design for reliable performance & maximum flexibility
  • Encapsulated for protection against harsh environments
  • Normally Open output rated 1A continuous/10A inrush is perfect for high duty cycle/long life applications
  • Universal input voltage of 24-240VAC or 12-125VDC
  • Onboard & remote adjustable or fixed time delays from 0.01 seconds to 100 hours
  • Pilot Duty Rating
Enclosure Style

Encapsulated 2" x 2" enclosure with single screw mounting

Configuration / Contact Rating
  • Normally Open
  • Solid State 1A Continuous, 10A Inrush @ 65° C
Application Information
  • Voltage Tolerance:
    • AC Operation: +10/-15% of nominal at 50/60 Hz
    • DC Operation: +10/-15% of nominal.
  • Load (Burden): Maximum of 1 VA for all voltages
  • Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%; Minimum Setting (Adjustable): +0%, -50%; Fixed Time Delay: +2% or 50ms, whichever is greater
  • Repeat Accuracy (Constant Voltage & Temperature): +0.1% or + 0.04 seconds, whichever is greater
  • Reset Time: 50ms
  • Output Contacts: Solid State 1A Continuous, 10A Inrush @ 65o C
  • Life: No predictable failure if used within operating parameters.

     

    Leakage Current (OFF-State): <5 mA @ 240VAC

    Minimum Load Current: 20mA

    Effective Voltage Drop (ON-State): Maximum 3V @ 1A for all voltages

  • Temperature: -28° to 65°C (-18° to 149°F)
Approvals
UL #: E236146

Operation

The cost effective design and compact size of the THS Series make them the ideal choice for many industrial applications. They utilize a microprocessor-based design for reliable performance & maximum flexibility. A Normally Open output rated 1A continuous & 10A inrush is perfect for high duty cycle/long life applications. All products are encapsulated for protection in harsh environments. Choose between adjustable or fixed time delays, either onboard or remote.

You May Be Interested in These Other Products

  • Function: Undercurrent only
  • Control Voltage: 24V AC/DC
  • Output: 10A SPDT
  • Trip Delay: 0.5-50 seconds
  • Enclosure Style: Encapsulated
  • Current Range: 5 - 50A
  • Sensing Delay On Power: 5 seconds
$138.82
  • Communication Platform: None
  • Monitored Voltage: 102-138V AC
  • Output: 10A SPDT
  • Protection: Phase Loss, Phase Reversal, Voltage Unbalance, Undervoltage & Overvoltage
  • Standard Modifications: None
  • Enclosure Style: Plug-in
$159.50
  • Control Voltage: 120V AC
  • Output: 4 Form C Contacts
  • Options: Standard (LED and Push-to-Test Included)
  • Terminal Configuration: Blade
$14.51