Description Of Function

As long as the monitored voltage (Un) remains within the OVER (Umax) & UNDER (Umin) voltage settings, the internal relay stays energized. If the monitored voltage falls outside this range, the relay will drop-out. The Umax dial sets the upper limit per the Overvoltage range of the product. The Umin dial sets the lower limit at 30-95% of the upper setting. This product has an adjustable time delay on drop-out of 0.1-10 seconds (t) to prevent nuisance tripping.

Function Chart

Product Overview

Features
  • Provides voltage band (window) protection
  • Wide range of user-adjustable Over Voltage and Under Voltage settings
  • 15A SPDT output contacts
  • Adjustable time delay on drop-out of 0.1 - 10 seconds
  • LEDs indicate nominal voltage & output relay status
Enclosure Style

17.5mm Modular for 35mm DIN-Rail Mounting

Configuration / Contact Rating
  • SPDT
  • 15A @ 240V AC, B300
Application Information
  • Voltage Tolerance: See table below; No supply (input) voltage is required.
  • Load (Burden): 3 VA (AC); 1.7W (DC)
  • Voltage Settings:
      VWKE024D VWKE120A VWKE240A
    Monitored Voltage (Un) 24V DC 120 VAC 240 VAC
    Overvoltage Range (Umax) 18-30V DC 80-150V AC 160-276V AC
    Undervoltage Range (Umin) 30-95% of Overvoltage Range (Umax)
  • LED Indication: Green-Monitored Voltage present; Red-Relay ON
  • Response Times: Pick-up: 100 ms; Drop-out: Adjustable 0.1-10 seconds
  • Output Contacts: 15A @ 240V AC, B300
  • Life: Mechanical: 10,000,000 operations; Full Load: 70,000 operations
  • Temperature: -30° to 70° C (-22° to 158° F)
Approvals
UL #: E466100

Operation

Bar graph with wavy lines

Provides protection to equipment that is required to operate within an upper & lower AC single phase or DC voltage limit. As long as the monitored voltage (Un) remains between the OVER (Umax) & UNDER (Umin) voltage settings, the internal relay stays energized. If the monitored voltage falls outside this range, the relay will drop-out. The Umax dial sets the upper trip setting per the Overvoltage range of the product. The Umin dial sets the lower trip setting at 30-95% of the upper setting. These products have an adjustable time delay on drop-out of 0.1-10 seconds (t) to prevent nuisance tripping. They have a compact 17.5mm enclosure which snaps on to 35mm DIN track. This conserves space & reduces installation time, which saves money.

voltage monitor

Watch the Voltage Monitor Relay Video

You May Be Interested in These Other Products

  • Communication Platform: Modbus TCP
  • Monitored Voltage: 190-600V AC
  • Output: 5A SPDT
  • Protection: Phase Loss, Phase Reversal, Voltage Unbalance, Undervoltage & Overvoltage
  • Standard Modifications: Local Adjustment (PC1MDUL);
  • Enclosure Style: DIN-Rail
$550.08
  • Function: Multi-Function (10): on delay (2 versions), interval (2 versions), flicker (2 versions), one-shot out flicker, off delay, on/off delay, integration time
  • Timing Range: Multi-range (10): 0.01 seconds - 9,990 hours
  • Timing Range 2: None
  • Timing Adjustment: Digital
  • Control Voltage: Universal: 24-240V AC and 24-240V DC
  • Output: 5A SPDT
  • Enclosure Type: 1/16 DIN
  • Standard Modifications: None
  • Remote Potentiometer: None
  • Remote Potentiometer 2: None
$161.58
  • Function: Undercurrent only
  • Control Voltage: 120V AC
  • Output: 10A SPDT
  • Trip Delay: 0.150-7 seconds
  • Enclosure Style: Encapsulated
  • Current Range: 5 - 50A
  • Sensing Delay On Power: 6 seconds
$138.82
  • Control Voltage: 120V AC/DC ( GS060C Relay & SS120 Socket)
  • Output: 6A 1 Form C
  • Options: None
  • Terminal Configuration: Slim (Pre-mounted with Socket)
$18.78