VWKP024D
Lead Time: 10 Days
Description Of Function
The relay energizes (and the LED is Red) when the monitored voltage is between the over and under voltage settings. The relay de-energizes (and the LED is Green) when the monitored voltage falls outside the over or under voltage settings for a period longer than the drop-out time delay (t), which is adjustable between 0.1-10 seconds. The relay re-energizes when the monitored voltage returns to a value between the over and under voltage settings for a period longer than the fixed pick-up time delay of 0.5 seconds.
Function Chart

Product Overview
Features
- Monitors AC single phase and DC voltages
- Provides voltage band (window) protection
- True RMS Sensing ensures more accurate sensing
- Wide range of user-adjustable Over Voltage and Under Voltage settings
- Adjustable time delay on drop-out
- Pilot Duty Rating
- LED indicates output relay status
Enclosure Style
Plug-in case utilizing industry-standard 8 pin octal sockets
Configuration / Contact Rating
- 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
Application Information
- Voltage Tolerance: +50%/-50% of nominal AC voltage (50-60Hz, +5%) or DC voltage; No separate input voltage is required since unit is powered by monitored voltage.
- Load (Burden): Less than 2 VA (12-120V); 30VA (240V & 480V)
- Voltage Settings:
Over Voltage (Umax): Adjustable across full range as shown on the product nameplate
Under Voltage (Umin): Adjustable from 75-95% of the Over Voltage setting - Response Times: Pick-up: 500 ms; Drop-out (t): Adjustable 0.1-10 Seconds
- Indicator LED: Red when Relay is energized; Green when Relay is Off
- Output Contacts: 10A @ 240V AC, 7A @ 30V DC, 1/4HP @ 120/240V AC, C300
- Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
- Temperature: -28° to 65° C (-18° to 149° F)
Approvals
Operation
Voltage Band Relays provide protection to equipment that is required to operate within an upper & lower voltage limit. As long as the operating voltage remains within an OVER & UNDER voltage range, the internal relay stays energized. If the operating voltage falls outside this range, the relay will drop-out.
Adjust the over voltage setting (Umax) between the full range as shown on the product nameplate. Adjust the under voltage setting (Umin) between 75% and 95% of the over voltage setting. The relay energizes (and the LED is Red) when the monitored voltage is between the over and under voltage settings. The relay de-energizes (and the LED is Green) when the monitored voltage falls outside the over or under voltage settings for a period longer than the drop-out time delay (t), which is adjustable from 0.1-10 seconds. The relay re-energizes when the monitored voltage returns to a value between the over and under voltage settings for a period longer than the pick-up time delay, which is fixed at 0.5 seconds.
File Downloads
-
Digital Catalog
-
VMP-VAKP-VWKP eCAD Package
CAD Drawing
-
901-0000-309 Instruction Sheet VMP, VAKP & VWKP Series