Description Of Function
Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized. Upon removal of the trigger, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Any application of the trigger during the time delay will reset the time delay (t) and the output remains energized.
Function Chart
Application Information
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.; DC Operation: +10/-15% of nominal.
Load (Burden): Maximum of 2 VA for all voltages
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%; Minimum Setting (Adjustable): +0%, -50%. Fixed: +2% or 50ms, whichever is greater
Output Contacts: 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.),1/3HP @ 120/240V AC (N.C.), B300 & R300
Life: Mechanical: 10,000,000 operations; Full Load: 100,000 operations
Temperature: (Storage) -40° to 85° C (-40° to 185° F); (Operating) (12-120V) -28o to 65o C (-18o to 149o F); 240V -28o to 50o C (-18o to 122o F)
Approvals:
Dimensions - Inches (Millimeters)
Contact Macromatic
Fill out this form to have Macromatic contact you about this product.
www.macromatic.com 800.238.7474
Product Specifications
TR-51628-12T5
Use socket: 70170-D
Image may not be exact product—for reference only.
Competitor: Agastat (Tyco)
Competitor Part #: SST22OEA
Series: SST22
Macromatic Equivalent: TR-51628-12T5
Differences: Also equivalent to Macromatic TR-6162U - which has 16 timing ranges built-in vs. one.
Family: TIME DELAY RELAY
Function: OFF DELAY (SWITCH TRIGGER)
Timing Range: 3-300 Sec
Input: 24V AC/DC
Output: 10A DPDT
Note: This product is subject to a 5 piece minimum per order. Please contact Macromatic for additional information.
Description of function:
Upon application of input voltage, the time delay relay is ready to accept a trigger. When the trigger is applied, the output is energized. Upon removal of the trigger, the time delay (t) begins. At the end of the time delay (t), the output is de-energized. Any application of the trigger during the time delay will reset the time delay (t) and the output remains energized.
Function Chart:
Application Information
Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz.; DC Operation: +10/-15% of nominal.
Load (Burden): Maximum of 2 VA for all voltages
Setting Accuracy: Maximum Setting (Adjustable): +5%, -0%; Minimum Setting (Adjustable): +0%, -50%. Fixed: +2% or 50ms, whichever is greater