ALTERNATING RELAYS

Alternating Relays equalize run times to increase equipment life and provide additional capacity. The alternating action is typically initiated by a control switch such as a float switch or pressure switch. Each time the initiating switch is opened, turning off a load, the alternating relay will change state, thus alternating the multiple loads.

Control the Run Time of Redundant Loads

Alternating relays are used in redundant load applications to equalize run times. These relays can also be used to run multiple loads simultaneously when additional capacity is needed. Duplex Controllers are used for S.O.S.O. operation, with three switch input and alternation of which pump is turned on first. If you need help picking the right relay, contact us.

 

DUPLEX CONTROL, PLUG-IN

ARP Series Relays ensure that multiple loads get equal run time by alternating between two loads. In a typical application, an idle standby unit is available in case the first unit fails. Alternating relays prevent deterioration of the idle unit by equalizing run time

S.O.S.O. OPERATION, PLUG-IN

ARP Duplex Series Relays combines functions of alternating relays, control relays & auxiliary contacts in one unit. The device offers sequence on – simultaneous off (S.O.S.O.) Operation with three float switch inputs. 

DUPLEX CONTROL, FLANGE

ARF Series Relays ensure that multiple loads get equal run time by alternating between two loads. The flange mounted enclosure is used for inner-door mounting. A back-mounted socket is included with the relay.

TRIPLEX CONTROL, PLUG-IN

ATP Series Relays control up to three loads with three switch input:  LEAD, LAG and LAG2. An optional top-mounted switch allows use as a Duplex relay until system expansion requires an additional third load. 

Enclosure Style
Function
Output
Control Voltage
Standard Modifications

Need a custom engineered product? We offer engineering assistance and quick turnarounds on prototypes.

FILTER BY MODEL NUMBER
SORT BY

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex SPDT w/ Selector Switch

Enclosure Style:

Plug-in

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$130.00

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex SPDT

Enclosure Style:

Plug-in

Standard Modifications:

None

$122.16

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired w/ Selector Switch (Control Voltage pins 5 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$133.72

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired (Control Voltage pins 3 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

None

$126.21

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired (Control Voltage pins 5 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

None

$126.21

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired w/ Selector switch; Square Socket (Control Voltage pins 3 and 7)

Enclosure Style:

12 Pin Square

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$172.88

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired; Square Socket (Control Voltage pins 3 and 7)

Enclosure Style:

12 Pin Square

Standard Modifications:

None

$165.19

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT Cross-Wired w/ Selector Switch (Control Voltage pins 3 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$133.72

ARP Duplex

Function: 

Duplex

Control Voltage

24V AC/DC

Output:

Duplex DPDT w/ Selector Switch

Enclosure Style:

Plug-in

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$133.72

ARP Duplex

Function: 

Duplex

Control Voltage

12V AC/DC

Output:

Duplex SPDT

Enclosure Style:

Plug-in

Standard Modifications:

None

$122.16

ARP Duplex

Function: 

Duplex

Control Voltage

12V AC/DC

Output:

Duplex DPDT Cross-Wired w/ Selector Switch (Control Voltage pins 5 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

Switch to select normal alternation or lock loads 1 or 2

$133.72

ARP Duplex

Function: 

Duplex

Control Voltage

12V AC/DC

Output:

Duplex DPDT Cross-Wired (Control Voltage pins 5 and 6)

Enclosure Style:

Plug-in

Standard Modifications:

None

$126.21

Frequently Asked Questions About Alternating Relays

 
 

Alternating Relay Downloads

ARF Series Alternating Relays Brochure

Alternating Relays Competitive Comparison

Alternating Relays

Knowledge Base Articles

Technical reports to answer your questions

Understanding A2L: There Are Code Changes That Need Consideration

Rapid Cycling of Control Switch Damages Large Pumps or Compressor Motors

Issue: How do I prevent a Bouncing Control Switch Due to Splashing Water from Rapidly Energizing One Load and Then the Other?   Solution/Resolution:  In Figure A, a single Control Switch could be susceptible to splashing water which would cause rapid opening & closing of the Control Switch.  Each time this

Interactive Competitive Cross-Reference

Did you know . . .

Troubleshooting for a Phase Reversal (Phase Sequence) Problem

Issue: I have purchased one of your three phase monitor relays and have connected it per the diagram on the unit. However, I cannot get the unit to operate–it just won’t turn on. What’s wrong? Solution/Resolution: Most problems when first installing and applying a three-phase monitor relay are due to

Need Answers? Look Here.

NEED A CUSTOM ENGINEERED PRODUCT

We offer engineering assistance for you unique applications, quick turnarounds on prototypes, and the best technical support in the industry

Custom engineered product

LOCATE A DISTRIBUTOR

If you have a need for a small quantity, our Authorized Distributors have many of our products in stock, ready for immediate shipment.  They can answer any questions you may have.