Answer:
The diagram illustrates a type of operation known as “Sequence On - Simultaneously Off (S.O.S.O. or SOSO)”- the two loads are energized sequentially, but remain on together until the OFF switch is opened. SOSO operation works best when using a DPDT Cross-Wired Alternating Relay. In the initial OFF state, all three switches are open, the Alternating Relay is in the LOAD 1 position, and both loads are off. No action happens with the Alternating Relay or either load when the OFF switch closes.
When the OFF Switch opens, both LOAD 1 and LOAD 2 are turned off simultaneously because all voltage is removed to both loads. Auxiliary contacts M1 & M2 both open. The Alternating Relay toggles to the LOAD 2 position. The entire cycle is then repeated, but with LOAD 2 energized first followed by LOAD 1. |